Generator sales, installation, parts, service, and maintenance

Varitech is proud to offer the highest quality OEM parts installed by our factory trained professionals. We provide the highest quality generator service and maintenance backed by our satisfaction guarantee.

parts • services • Preventative Maintenance •
parts • services • Preventative Maintenance •
parts • services • Preventative Maintenance •

generator system services

Our business and reputation is built on customer service. Our goal is to build long term relationships by providing our customers with uncompromising parts, service, and support 24 hours a day, 7 days a week. Our technicians are trained and certified to troubleshoot and correct problems on any generator system. They have hundreds of hours of training and many years of experience servicing power generation systems.

Parts

We carry and stock many parts for both Generac and Briggs & Stratton generators.

In the event that necessary parts are not in inventory, we can often get them the next day.



Learn More >

Service

Our professional team of technicians service a wide range of Generator Systems including Generac, Briggs & Stratton, Eaton, Carrier, Kohler, CAT, Cummins Onan and more.

Learn More >

maintenance

Our scheduled maintenance program helps ensure your standby generator provides the security, protection and reliability that you demand. Our customer database tracks your equipment service records so that we can provide the right service at the right time.

Learn More >

Diesel Fuel Reconditioning and Polishing Services

Emergency power is critical when disaster or storms strike. Are you really prepared? Experience has shown that diesel fuel stored to operate emergency generators is often neglected. Generator manufacturers report that over half of generator failures are due to degraded diesel fuel issues. Diesel quality can quickly deteriorate and become unusable when stored for months and years at a time. When called upon during an emergency, this degraded fuel can plug filters, damage engine fuel system components and ultimately disable your emergency generator system.

The solution is Fuel Polishing. Fuel polishing is a process of water removal, filtering the solids that naturally occur when fuel is stored and treating the fuel with additives that restore fuel to new condition.

Load bank testing
services

Most critical applications require standby generator systems, however they are rarely tested under full load conditions. How much faith do you have that your system will perform in a real emergency?

We provide Load Bank Testing that can test your generator completely through all conditions up to and including full rated output without affecting your critical load. In addition, this test helps seat piston rings, can eliminate wet stacking, removes harmful carbon deposits and helps you comply with NFPA & Joint Commission requirements, all within a controlled environment.

Parts

We carry and stock many parts for both Generac and Briggs & Stratton generators.In the event that necessary parts are not in inventory, we can often get them the next day.

Since we are an authorized dealer for the brands we carry, our parts are fully covered by the warranties set by the manufacturers.

Varitech offers a wide range of OEM parts and accessories at competitive prices so you can ensure you are getting quality products at prices you can afford.

For more information about our parts inventory or to order parts for you generator, please contact our team today.

502-966-3400

SERVICE

Our professional team of technicians service a wide range of Generator Systems including Generac, Briggs & Stratton, Eaton, Carrier, Kohler, CAT, Cummins Onan and more.

We provide Load Bank Testing that can test your generator completely through all conditions up to and including full rated output without affecting your critical load. In addition, this test helps seat piston rings, can eliminate wet stacking, removes harmful carbon deposits and helps you comply with NFPA & Joint Commission requirements, all within a controlled environment.

Varitech also offers many other services including fueling service. All services, repairs and PMs include a detailed service report for your records. We also maintain a service file for all of our customers, in the event that yours are ever lost or destroyed.

MAINTENANCE

Maintenance helps ensure that your standby generator provides the security, protection and reliability that you deserve. Our customer database tracks your equipment service records.

You have the peace of mind knowing that we will contact you when service is due—one less thing you have to keep track of.

You can choose your own level of protection, but at a minimum we recommend Semi-Annual Services consisting of a Level A Inspection visit and a Level B Service visit in alternating 6-month intervals. Our Annual Service consists of a single Level B visit every 12 months.

DIESEL FUEL RECONDITIONING AND POLISHING SERVICES

Emergency power is critical when disaster or storms strike. Are you really prepared? Experience has shown that fuel stored to operate emergency generators is too often neglected. Generator manufacturers report that over half of generator failures are due to degraded fuel issues. Fuel quality can quickly deteriorate and become unusable when stored for months and years at a time. When called upon during an emergency, this degraded fuel can plug filters, damage engine fuel system components and ultimately disable your emergency generator system.

The solution is Fuel Polishing. Fuel polishing is a process of water removal, filtering the solids that naturally occur when fuel is stored and treating the fuel with additives that restore fuel to new condition.

LOAD TESTING
SERVICES

Most critical applications require standby generator systems, however they are rarely tested under full load conditions. How much faith do you have that your system will perform in a real emergency?

We provide Load Bank Testing that can test your generator completely through all conditions up to and including full rated output without affecting your critical load. In addition, this test helps seat piston rings, can eliminate wet stacking, removes harmful carbon deposits and helps you comply with NFPA & Joint Commission requirements, all within a controlled environment.

Trust in the LORD with all your heart and lean not on your own understanding; in all your ways submit to him, and he will make your paths straight.
Proverbs 3:5-6

ANNUAL
SERVICE

  • REPLACE engine oil filter(s) and CHANGE engine oil.

  • Inspect, clean or replace air filter(s) as needed.

  • Replace fuel filter(s) or clean fuel strainer(s) as required.

  • Inspect and test cooling system.

  • Replenish or replace coolants and rust inhibitors as required.

  • Check block heater operation.

  • Inspect all belts, hoses and guards.

  • Inspect, test and service batteries, cables and terminals.

  • Check starting system.

  • Check charging system.

  • Inspect wiring and control panel.

  • Inspect, clean, and lubricate the generator as required.

  • Inspect and adjust the transfer switch.

  • Check fuel level.

  • Start and run system.

  • Check operation of meters and gauges.

  • Check and record system run data.

  • Test fault shutdowns.

  • Transfer load to system (with customer authorization.)

  • Provide a written report on the condition of the system.

  • We can even include topping off your fuel supply on diesel models.

semi-annual
services

  • INSPECT engine oil filter(s) and ADD engine oil.

  • Inspect, and clean air filter(s) as needed.

  • INSPECT fuel filter(s) or clean fuel strainer(s) as required.

  • Inspect and test cooling system.

  • Replenish or replace coolants and rust inhibitors as required.

  • Check block heater operation.

  • Inspect all belts, hoses and guards.

  • Inspect, test and service batteries, cables and terminals.

  • Check starting system.

  • Check charging system.

  • Inspect wiring and control panel.

  • Inspect, clean, and lubricate the generator as required.

  • Inspect and adjust the transfer switch.

  • Check fuel level.

  • Start and run system.

  • Check operation of meters and gauges.

  • Check and record system run data.

  • Test fault shutdowns.

  • Transfer load to system (with customer authorization.)

  • Provide a written report on the condition of the system.